PUMP
Recommendation
PUMP-Rec-01 Rev C
PUMP RECOMMENDATION FOR
ARMOR 151-200 WATER HEATER
Pump Specifications
Part No.
HorsePower
Flanges
Valute Material
Flange Material
Vendor
Vendor Product Series
Orientation
PUM3010
1/6
1-1/4"
Bronze
Bronze
Armstrong
E Series
Vertical
Installation Specifications
Recommended for
Model Numbers
Armor Wtr Htr, AW(N,L) 151-200
Based on
Based on
Installation Type
Single Water Heater piped to Single Storage Tank
Pump
Minimum GPM
16 GPM (151) & 21 GPM (200)
Based on
PUM3010
Minimum Pipe Diameter
Connecting piping
1-1/4"
Maximum 45 feet straight pipe with 4-Elbows, 2-Unions and 2-Ball Valves
IMPORTANT: Read the Armor 151-801 Installation and Operation Manual. If the planned system exceeds
the pump capacity in flow and/or head see “Pump Curves-All Pumps” for alternate pumps and pump curves.
1
PUMP
Recommendation
PUMP-Rec-01 Rev C
PUMP RECOMMENDATION FOR
ARMOR 400 WATER HEATER
Pump Specifications
Part No.
HorsePower
Flanges
Valute Material
Flange Material
Vendor
Vendor Product Series
Orientation
PUM3012
2/5
1-1/2"
Bronze
Bronze
Armstrong
E Series
Vertical
Installation Specifications
Recommended for
Based on
Pump
Model Numbers
Minimum GPM
39 GPM (400)
Installation Type
Single Water Heater piped to Single Storage Tank
Armor Wtr Htr, AW(N,L) 400
PUM3012
Based on
Based on
Connecting piping
Maximum 45 feet straight pipe with 4-Elbows, 2-Unions and 2-Ball Valves
Minimum Pipe Diameter
2"
IMPORTANT: Read the Armor 151-801 Installation and Operation Manual. If the planned system exceeds
the pump capacity in flow and/or head see “Pump-Curves-All Pumps” for alternate pumps and pump curves.
3
PUMP
Recommendation
PUMP-Rec-01 Rev C
PUMP RECOMMENDATION FOR
ARMOR 501-601 WATER HEATER
Pump Specifications
Part No.
HorsePower
Flanges
Valute Material
Flange Material
Vendor
Vendor Product Series
Orientation
PUM30003
2/5
2"
Bronze
Bronze
Armstrong
E Series
Vertical
Installation Specifications
Recommended for
Model Numbers
Armor Wtr Htr, AW(N,L) 501-601
Based on
Based on
Installation Type
Single Water Heater piped to Single Storage Tank
Pump
Minimum GPM
53 GPM (501) & 53 GPM (601)
Based on
PUM30003
Minimum Pipe Diameter
Connecting piping
2"
Maximum 45 feet straight pipe with 4-Elbows, 2-Unions and 2-Ball Valves
IMPORTANT: Read the Armor 151-801 Installation and Operation Manual. If the planned system exceeds
the pump capacity in flow and/or head see “Pump-Curves-All Pumps” for alternate pumps and pump curves.
4
PUMP
Recommendation
PUMP-Rec-01 Rev C
PUMP RECOMMENDATION FOR
ARMOR 701-801 WATER HEATER
Pump Specifications
Part No.
HorsePower
Flanges
Valute Material
Flange Material
Vendor
Vendor Product Series
Orientation
PUM30004
3/4
2"
Bronze
Bronze
Grundfos
Versa Flow TP40-160
Vertical
Installation Specifications
Recommended for
Model Numbers
Armor Wtr Htr, AW(N,L) 701-801
Based on
Based on
Installation Type
Single Water Heater piped to Single Storage Tank
Pump
Minimum GPM
63 GPM (701) & 67 GPM (801)
Based on
PUM30004
Minimum Pipe Diameter
Connecting piping
2"
Maximum 45 feet straight pipe with 4-Elbows, 2-Unions and 2-Ball Valves
IMPORTANT: Read the Armor 151-801 Installation and Operation Manual. If the planned system exceeds
the pump capacity in flow and/or head see “Pump-Curves-All Pumps” for alternate pumps and pump curves.
TP 40-160
5
|
Leica Laser Level 6007282 User Manual
Leica Microscope Magnifier M60 User Manual
Leica Microscope Magnifier MS5 User Manual
Liebert Power Supply GXT2 10000RT208 User Manual
Lincoln Electric Welder IM10059 User Manual
Logitech Video Game Keyboard K28Oe User Manual
Magnavox Cassette Player AQ 6481 User Manual
Magnavox TV VCR Combo MC09D5MG User Manual
Manitowoc Ice Ice Maker K00363 User Manual
McCulloch Chainsaw 414 User Manual